For the voltage supply of electronic circuit protection modules. For the permanent monitoring of the 24 V secondary circuit. Reliable switch-off in case of a fault. Modular and selective protection of machinery and plant. Simple side-by-side installation due to flap mechanism
Operating voltage [V]
to SELV/PELV
Nominal voltage DC [V]
24
Input voltage DC [V]
19.2...30
Protection class
III
Reverse polarity protection
yes
Mains buffering time (nominal voltage 24 V DC) [ms]
10
Input current (nominal voltage 24 V DC) [A]
40
Closed-circuit current [mA]
10
Interfaces
Communication interface
IO-Link
Transmission type
COM2 (38,4 kBaud)
IO-Link revision
1.1
SIO mode
no
Min. process cycle time [ms]
20
Supported DeviceIDs
Type of operation
DeviceID
default
892
Note
For further information please see the IODD PDF file under "Downloads"
Operating conditions
Ambient temperature [°C]
-25...60
Storage temperature [°C]
-40...70
Protection
IP 20;(on the front)
Pollution degree
2
Tests / approvals
EMC
EN 61000-6-3
radiation of interference
EN 61000-6-2
immunity
Weight [g]
73
Dimensions [mm]
80 x 12.5 x 98
Displays / operating elements
Display
status
1 x LED, red / green / orange
Electrical connection
Connection
push-in terminals:
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — EN-GB — DF2101-00 — 29.09.2017 —