1
/
of
1
Dold
Dold IN5880.12/711 AC50-400HZ 220-240V, Insulation monitor, sku: 0056884
Dold IN5880.12/711 AC50-400HZ 220-240V, Insulation monitor, sku: 0056884
Regular price
€839,49
Regular price
Sale price
€839,49
Unit price
/
per
Taxes included.
📦 Ready for dispatch: 31.12.2025
Couldn't load pickup availability
SKU: SKU:0056884
For insulation monitoring of the IT system of rooms used for medical purposes according to VDE 0100-710.
| Width: | 52,5 mm |
| Classification: | For medically used rooms |
| Response value: | 50 - 500 kΩ |
| IMD type: | AC |
| Nominal voltage IT system: | AC 0 - 500 V |
| Auxiliary voltage: | AC |
| Earth fault indicator: | Yes |
| Response value type: | Adjustable |
| Enclosure design: | Distribution board |
| Type: | IN 5880/711 |
- According to IEC/EN 61 557-8
- For rooms used for medical purposes
according to IEC 60364-7-710, DIN VDE 0100-710 - For three-phase and A.C. power systems with 0 … 500 V
and 10 … 1000 Hz (IT power systems) - Adjustable alarm value for ground fault RAL of 50 … 500 kΩ
- Measuring circuit with broken wire protection
- As option, programmable for storing or non-storing of errors
- With reset and test button
- Additional external reset and test buttons can be connected
- LED indicators for operation, insulation fault, and interruption of Measuring circuit
- 2 changeover contacts
- With LED chain for indication of the current insulation status
- IP 5880/711 for connection of the test and display panel UP 5862
- 52.5 mm width