For applications in hazardous areas. Reliable monitoring of aggressive liquids in pipes. For connection to an evaluation unit. Ceramic materials for contact with the medium. Robust design for use in harsh industrial environments
Probe length L [mm]
30
Process connection
G 1/2 external thread
Media
Liquids; aggressive media
Medium temperature [°C]
5...70
Pressure rating [bar]
30
Liquids
Medium temperature [°C]
5...70
Connection to control monitor
VS2000 Exi (PTB 01 ATEX 2075)
Measuring/setting range
Probe length L [mm]
30
Liquids
Setting range [cm/s]
3...60
Greatest sensitivity [cm/s]
3...40
Accuracy / deviations
Temperature gradient [K/min]
7
Response times
Response time [s]
2...20
Liquids
Response time [s]
2...20
Operating conditions
Ambient temperature [°C]
-20...70
Protection
IP 67
Tests / approvals
Approval
DMT 03 ATEX E091; IECEX BVS 06.0007
ATEX marking
II2GEx ia IIC T4 Gb
Shock resistance
DIN IEC 68-2-27
40 g (11 ms)
Vibration resistance
DIN IEC 68-2-6
10 g (55...2000 Hz)
MTTF [years]
7927
Safety classification
Max. internal capacitance [nF]
1.2
Max. internal inductance [µH]
6
Temperature class
T4
Weight [g]
353
Housing
threaded type
Materials
ceramics (99.7 % Al2O3)
Materials (wetted parts)
ceramics (99.7 % Al2O3)
Process connection
G 1/2 external thread
Installation length EL [mm]
45
Remarks
In principle, the type test according to 94/9/EC (ATEX) only takes atmospheric conditions into account (0.8...1.1 bar).
For pressures outside this range use must be assessed and approved by the user.
Adhere to the operating instructions and the type test certificate.
Pack quantity
1 pcs.
Electrical connection
Connection
Cable: 6 m, TPE-S; Maximum cable length: 100 m; 5 x 0.34 mm²